Armstrong SH-1500 Series bimetallic steam traps are designed for superheat and low-load applications. Featuring a titanium valve and seat, they handle up to 124 bar at 565°C.

Armstrong SH-1500 Series superheat steam traps operate by the effect that rising temperature has on the thermostatic bimetallic elements. At start-up, the valve is wide open, which allows a large volume of non-condensables and cold condensate to be removed from the system. When the system reaches steam temperature, the elements become sufficiently hot to pull on the trap’s valve stem, closing the valve.

The valve remains closed until the bimetallic elements cool, thus allowing the valve to crack open, vent the condensate and non-condensables, and then close again when steam temperature is reached. The SH Series superheat steam traps adjust automatically to changing conditions. Hot elements in the valve generate forces to offset rises in pressure. The SH-1500 series utilizes titanium valves and seats to ensure extremely long service life in the harsh environment of superheated steam systems.
Bimetallic style steam traps type SH-1500 are constructed in investment cast chromemoly steel with an integral stainless steel strainer and are inline repairable. The mechanism consists of a stacked nickel-chrome bimetal operator with a titanium valve and seat. The steam trap is capable of operation on low-load applications throughout its pressure/temperature range.
| Condition | Value |
|---|---|
| Maximum allowable pressure (vessel design) | 124 bar @ 565°C |
| Maximum operating pressure | 124 bar |
| Maximum back pressure | 99% of inlet pressure |
| Suggested minimum operating pressure | 41 bar |
| Component | Material |
|---|---|
| Connections | 20 – 25 mm: Buttweld, Flanged EN 1092-1 or ASME B16.5 |
| Body and Cap | ASTM 217 Gr. C12A |
| Valve & Seat | Titanium |
| Bimetallic Elements | Nickel-chrome and stainless steel |
| Strainer | Stainless Steel Screen |

| Model | SH-1500 | SH-1500 |
|---|---|---|
| Pipe Connections (mm) | 20 | 25 |
| “B” (Height BW) in mm | 129 | 129 |
| “C” (Face-to-face BW - with extended nipples) in mm | 157 | 157 |
| “D” (Centerline to Top) in mm | 98 | 98 |
| “E” (Width) in mm | 123 | 123 |
| “F” (Face-to-face Flanged ANSI 1500#) in mm | 475 | 481 |
| “G” (Height Flanged ANSI 1500lbs) in mm | 163 | 173 |
| Weight in kg (BW) | 10.4 kg | 10.4 kg |
| Weight in kg (Flanged ANSI 1500#) | 16.5 kg | 18.5 kg |
INFO
Standard flanges are in carbon steel; stainless steel flanges are optional. Other flange sizes, ratings, and face-to-face dimensions are available on request. All sizes comply with Article 4.3 of the PED (2014/68/UE).
Cold Water Capacity
Hot Condensate Capacity
WARNING
Equipment under pressure - Operating temperature > 100°C - Make sure the trap is cold before handling!