Skip to content
Stepper Motor DrivenIntegrated PositionerZero Standby Power

BURKERT 20032566 3281 Electromotive 2-Way Globe Proportional Valve

Burkert Type 3281 electromotive 2-way globe proportional valve with integrated positioner or process controller. Features stepper motor, DN15, up to 130°C.

BURKERT 20032566 3281 Electromotive 2-Way Globe Proportional Valve

The Burkert Type 3281 direct-acting electromotive 2-way proportional valve is particularly suitable for dosing liquids and gases in closed or open control loops. The valve is driven by a linear stepper motor. The integrated electronics assembly simplifies process integration, meaning additional actuation modules are not necessary. The motor does not need any energy to maintain a certain valve opening. This feature can reduce the energy consumption of a plant dramatically and therefore make it more efficient.

The Type 3281 is available as a variant with an integrated positioner, as well as a variant with an integrated process controller. The valve spindle is rigidly connected to the threaded spindle and driven by the stepper motor, converting rotary movement into linear movement to regulate flow.

Key Features:

  • Actuator is not wetted by the medium
  • Excellent setting range and fast reaction time
  • Connection orifice DN 15
  • Medium temperature up to +130 °C
  • Variants: positioner, process controller

General Technical Data

Product PropertiesSpecification
SealPTFE
Valve bodyStainless steel
Flow directionAgainst closing direction (below seat)
DesignGlobe: on/off valve or control valve
Angle seat: on/off valve or control valve
Weight~1.1 kg
OrificeDN 15, NPS 1/2
Controller variantOn/off valve or position controller or process controller
Dead band of position control±0.5% (corresponds to setting range 1:100)
Closing time2.5 s
Operating pressure0...16 bar(g) (depending on seat size)
Vacuum variant up to -0.9 bar(g) (optional)
Duty cycleUp to 100% (depending on medium and ambient temperature)
Kvs value0.57...4.55 m³/h
Nominal pressurePN 25 (DIN EN 1333)
Seat leakageClass VI (DIN EN 60534-4)
Operating voltage24 V DC ± 10% (max. residual ripple 10%)
Power consumption<1 W holding power
Max. 12 W (short term 20 W)
Operating mediumNeutral gases and liquids
Medium temperature-20 °C...+130 °C
ViscosityMax. 600 mm²/s (cSt)
Degree of protectionIP54

Energy Efficiency

The stepper motor is only supplied with energy when it opens or closes the valve further. Owing to the internal holding torque, the stepper motor only moves when it is controlled. In the remaining time, only the control electronics need a basic voltage supply.

Materials

BURKERT 20032566 Burkert 3281 actuator material specifications

No.ElementMaterial
1Housing coverPC (Polycarbonate)
2Housing basePPS (Polyphenylenesulfide)

BURKERT 20032566 Burkert 3281 valve body material specifications

No.ElementMaterial
3Spindle guideHigh-performance polymer
4Sliding washersHigh-performance polymer
5Guide pieceStainless steel 1.4305
6O-ringNBR
7Compression springStainless steel
8Spindle sealPTFE (filled)/FKM, with spring compensation
9PipeStainless steel 1.4404
10Body sealGraphite
11SpindleStainless steel 1.4401
12Control cone/swivel plateStainless steel 1.4571
13Seat sealPTFE sealing washer
14Valve seatStainless steel 1.4571
15Valve bodyStainless steel CF3M/316L

Dimensions

Globe Variant Actuator

BURKERT 20032566 Burkert 3281 globe variant dimensions

ABCDEFGHIJ
76216188841125266455820

(Dimensions in mm. Twisting of the actuator housing is possible.)

Performance Specifications

Duty Cycle Derating

The duty cycle is an important factor for motor valves. The self-heating of the engine limits the maximum duty cycle. High ambient temperatures additionally increase the risk of damage due to overheating. The following diagram shows the recommended maximum duty cycle as a function of the ambient temperature.

Duty Cycle Limits

Operating the valve outside the recommended duty cycle limits will result in a significantly reduced service life of the valve. The duty cycle refers to the motor, which is only switched on when the valve is to move.

BURKERT 20032566 Burkert 3281 duty cycle derating diagram

Pressure Range (Standard Variant)

Valve functionSeat sizeController variantPort connectionKvs value [m³/h]Pressure range [bar(g)]
Globe (Control)4ControlG 1/20.570...16
Globe (Control)6ControlG 1/21.250...16
Globe (Control)8ControlG 1/21.80...12
Globe (Control)10ControlG 1/22.250...7
Globe (On/off)15On/offG 1/24.450...3.5
Angle-seat (Control)15ControlG 1/23.60...3
Angle-seat (On/off)15On/offG 1/24.550...3.5

Flow Characteristic

The dimensioning of the seat size is very important for electromotive proportional valves to function properly within the application. The seat size must be selected so that the desired flow range is achieved and, when the valve is fully open, a sufficient portion of the total pressure drop occurs across the valve (Reference value: Δp valve > 25% of the total pressure drop).

BURKERT 20032566 Burkert 3281 linear flow characteristic curve

Product Operation

Positioner Variant

The proportional valve in the position control variant converts an external standard signal, the position set-point value, into a valve position. The position of the actuator is controlled according to the set-point position. The position sensor records the current position (POS) of the electromotive valve. This actual position is compared by the positioner with the set-point value (CMD) specified as the standard signal. If there is a control difference, a motor control signal is given to the actuator as the actuating variable.

BURKERT 20032566 Burkert 3281 process diagram for positioner variant

Process Controller Variant

The additionally implemented PID controller can perform not only the actual position control but also a process control in the sense of a cascade control. The process controller is integrated into a control loop. The position setpoint of the valve is calculated from the process setpoint and the actual process value via the control parameters (PID controller).

BURKERT 20032566 Burkert 3281 process diagram for process controller variant

BURKERT 20032566 Burkert 3281 signal flow diagram for process controller