TLV FV-200 carbon steel condensate flash vessel for recovering flash steam from high-pressure steam systems. Max 16 barg, 260°C. Also covers FV-300 and FV-400.

The TLV FV-200 is a carbon steel condensate flash vessel designed to provide a simple and efficient method to make use of flash steam in the condensate recovery system. It is utilized for the recovery and economic recycling of flash steam from high-pressure steam-using equipment. The vessel features low flow velocities for optimal steam quality and is designed in accordance with the Pressure Equipment Directive 2014/68/EU. The FV series also includes the larger FV-300 and FV-400 models.
An optional complete flash recovery system is available, including all necessary valves to control and safeguard the condensate line (consult TLV for details).
Classification according to PED 2014/68/EU, fluid group 2:
| Model | Category | CE Marking |
|---|---|---|
| FV-200 | 1 | With CE marking and Declaration of Conformity |
| FV-300 | III | With CE marking and Declaration of Conformity |
| FV-400 | III | With CE marking and Declaration of Conformity |

| Model | FV-200 | FV-300 | FV-400 |
|---|---|---|---|
| Body Material | 1.0345 (P235GH) | 1.0345 (P235GH) | 1.0345 (P235GH) |
| Connection | Flanges acc. to DIN EN 1092-1 Type 11 PN40 | Flanges acc. to DIN EN 1092-1 Type 11 PN40 | Flanges acc. to DIN EN 1092-1 Type 11 PN40 |
| Size (DN) | See "Connections" | See "Connections" | See "Connections" |
| Max. Operating Pressure (barg) PMO | 16 | 16 | 16 |
| Max. Operating Temperature (°C) TMO | 260 | 260 | 260 |
| Approx. Volume (L) | 30 | 70 | 140 |
| Applicable Fluid* | Steam/Condensate | Steam/Condensate | Steam/Condensate |
Operating Limits
PRESSURE SHELL DESIGN CONDITIONS (NOT OPERATING CONDITIONS):

To avoid abnormal operation, accidents or serious injury, DO NOT use this product outside of the specification range. Local regulations may restrict the use of this product to below the conditions quoted.
| Model | L (DIN EN 1092-1 PN40) | φD | H | H1 | H2 | Weight* (kg) |
|---|---|---|---|---|---|---|
| FV-200 | 530 | 219.1 | 1515 | 685 | 945 | 36 |
| FV-300 | 640 | 323.9 | 1653 | 685 | 1005 | 60 |
| FV-400 | 730 | 406.4 | 1902 | 711 | 1111 | 108 |
| Model | Inlet A | Outlet B | Exhaust C | Drain D | Process Connections |
|---|---|---|---|---|---|
| FV-200 | DN 100 | DN 40 | DN 80 | DN 25 | 1x G 1/2", 2x G 3/4" |
| FV-300 | DN 125 | DN 50 | DN 125 | DN 25 | 1x G 1/2", 2x G 3/4" |
| FV-400 | DN 150 | DN 50 | DN 150 | DN 25 | 1x G 1/2", 2x G 3/4" |


5,500 kg/h condensate from a 5 barg steam consumer should be expanded to 2 barg. Approx. 277 kg/h flash steam is generated. A suitable condensate flash vessel must be selected. Move from the 5,500 kg/h condensate volume horizontally to the right and from the 277 kg/h flash steam volume vertically upwards. Since the point of intersection is within the area of the FV-300, the flash vessel FV-300 must be selected.
With a condensate quantity of 11,000 kg/h, the pressure should be reduced from 12 barg to 2 barg. This produces approx. 1,286 kg/h of flash steam. A suitable condensate flash vessel must be selected. Move from the 11,000 kg/h condensate volume horizontally to the right and from the 1,286 kg/h flash steam volume vertically upwards. Since the point of intersection B is within the area of the FV-400, the flash vessel FV-400 must be selected.