Skip to content
316L Stainless SteelSelf-DrainingClean SteamPED Compliant

Armstrong 洁净蒸汽热静力蒸汽疏水阀 – TC 系列 TC Series Thermostatic Clean Steam Traps

Armstrong TC Series thermostatic clean steam traps (TC-C, TC-R, TC-S) are constructed of 316L stainless steel. Self-draining and highly polished for sterile applications.

Armstrong 洁净蒸汽热静力蒸汽疏水阀 – TC 系列 TC Series Thermostatic Clean Steam Traps

Armstrong TC Series thermostatic clean steam traps are designed to handle the special requirements of clean steam systems. The series includes the T-316L stainless steel TC-C, TC-R, and TC-S models, which offer different body configurations to allow for a choice of piping and ease of cleaning. The thermostatic design is free-draining and can operate close to steam temperature at any given pressure. Additionally, the TC-300 series is specifically designed for instrument tracing with extremely low condensate loads.

Features and Applications

Features:

  • Constructed of 316L stainless steel for corrosion resistance (TC-C, TC-R, TC-S)
  • Highly polished for cleanability
  • Self-draining to minimize contamination
  • Compact and lightweight
  • Easy to install and disassemble for cleaning

Typical Applications:

  • Fermentors and Bioreactors
  • Sterilizers/autoclaves
  • Process piping
  • Block and bleed
  • CIP/SIP systems
  • Equipment sterilization and sterile barriers

Model Variants

  • Model TC-C: Clamp with sanitary body clamp. Available with 1/2", 3/4", and 1" sanitary end connections. Armstrong 洁净蒸汽热静力蒸汽疏水阀 – TC 系列 Armstrong TC Series Model TC-C Clamp with sanitary body clamp
  • Model TC-R: Repairable with bolted body and cap. Available with sanitary, threaded, or tube end connections. Armstrong 洁净蒸汽热静力蒸汽疏水阀 – TC 系列 Armstrong TC Series Model TC-R Repairable with bolted body and cap
  • Model TC-S: Sealed design. Available with sanitary, threaded, or tube end connections. Armstrong 洁净蒸汽热静力蒸汽疏水阀 – TC 系列 Armstrong TC Series Model TC-S Sealed sanitary end connections
  • Model TC-300: Thermostatic diaphragm trap for instrument tracing. Armstrong 洁净蒸汽热静力蒸汽疏水阀 – TC 系列 Armstrong TC Series TC-300 thermostatic diaphragm trap

Materials and Specifications

TC-C, TC-R, and TC-S (Clean Steam)

ModelTC-C ClampTC-R RepairableTC-S Sealed
Cap and body316L stainless steel316L stainless steel316L stainless steel
Bellows316L stainless steel316L stainless steel316L stainless steel
Body gasketVitonViton
Retainer316L Stainless steel316L Stainless steel316L Stainless steel
Clamp / Screws304 SS Clamp304 SS Screws
Interior Finish≤ 0.5 μm Ra≤ 0.5 μm Ra≤ 1.6 μm Ra
Exterior Finish≤ 0.8 μm Ra≤ 0.8 μm Ra≤ 0.8 μm Ra
Physical DataTC-C ClampTC-R RepairableTC-S Sealed
Max Allowable Pressure8.3 bar (120 psig)8.3 bar (120 psig)10 bar (150 psig)
Max Allowable Temp177°C (350°F)177°C (350°F)186°C (366°F)
Max Operating Pressure7 bar (100 psig)7 bar (100 psig)8.3 bar (120 psig)
Weight0.57 kg0.68 kg0.34 kg

TC-300 (Instrument Tracing)

SpecificationTC-300
ConnectionsBSPT Threaded, Socket Weld, Flanged
Body / Cap MaterialCarbon Steel
Internals Material304 Stainless Steel
Max Allowable Pressure2.4 MPa @ 350°C
Max Operating Pressure2.4 MPa

Capacities

TC-C, TC-R, and TC-S Capacities

Differential Pressure (bar)5°C Subcool (kg/h)11°C Subcool (kg/h)
0.3582145
0.7163293
1.4307503
2.1458709
2.8561830
3.5699915
4.18371,136
4.89241,210
5.51,0711,356
6.21,1161,468
6.91,1551,565
7.61,1841,651
8.31,2061,712

INFO

Capacities based on differential pressure with no back pressure. Capacities will vary with the degree of subcooling. When greater capacities are required, the trap will automatically adjust to the load, up to the maximum (cold water) capacity shown, by increasing the amount of subcooling.

TC-300 Capacities

Differential Pressure (MPa)Cold Water 21°C (kg/h)Hot Water 100°C (kg/h)10°C Subcool (kg/h)
0.03554454.5
0.0768775.9
0.141451138.2
0.3522218111.8
0.729526315.9
1.0531831818.1
1.440836320.9
1.745443122.7

Installation and Maintenance

Installation

The Clean Steam Traps are intended to be installed in vertical lines with downward flow in order to ensure that the trap is self-draining. Verify that the flow direction arrow on the trap is in the correct downward position. If the steam trap has sanitary end connections, do not over-tighten clamps during installation.

Maintenance Safety

Equipment under pressure - Operating temperature > 100°C. Make sure the trap is cold before handling!

Thermostatic Element Replacement (TC-C and TC-R):

  1. Remove the complete trap from the steam line.
  2. Open and remove the clamp (TC-C) or unscrew the bolts (TC-R) and lift the cap.
  3. Remove the gasket and the thermostatic element assembly.
  4. Clean trap cap and body if necessary.
  5. Replace the gasket and the thermostatic element assembly.
  6. Put the cap back on the body and secure the clamp or bolts.

INFO

Model TC-S sealed traps are a welded non-repairable design and must be replaced when the trap's service life has expired.