BURKERT 20016285 (Type 8652) 12-Slot AirLINE Valve Island, Industrial Ethernet, AirLINE Quick Aluminium

BURKERT 20016285 (Type 8652) is a 12-slot AirLINE pneumatic valve island with Industrial Ethernet, AirLINE Quick aluminium adapter plate, brass D10/D6 ports, SIA safety shut-off, and IP20 rating.

BURKERT 20016285 (Type 8652) 12-Slot AirLINE Valve Island, Industrial Ethernet, AirLINE Quick Aluminium

BURKERT 20016285 (Type 8652) is a 12-slot AirLINE pneumatic valve island configured for process automation applications, featuring an integrated Industrial Ethernet fieldbus interface supporting PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic via dual RJ45 ports. Built on an anodised aluminium AirLINE Quick adapter plate, article 20016285 integrates brass push-in connections with D10 mm supply ports and D6 mm working ports. The unit operates with internal auxiliary pilot air over a nominal operating pressure range from -1.00 bar to 10.00 bar and pilot pressure from 3.00 bar to 10.00 bar. Two valve positions incorporate SIA functionality (safety-related shut-off) to isolate individual pneumatic circuits upon external interlock tripping.

Diagnostic messages and operational statuses are presented on an integrated backlit LC display in both clear text and standardized symbols, while remaining concurrently accessible to the higher-level PLC over fieldbus communication. The mechanical form factor is optimized for control cabinet base and wall cutout mounting via AirLINE Quick, providing IP65 ingress protection within closed cabinets.

Factory Configuration of Article 20016285 ​

Article 20016285 is supplied factory-assembled with 12 active pneumatic valve slots utilizing 11 mm Type 6534 solenoid pilot valves. The position-by-position allocation is defined below:

Valve PositionCircuit FunctionDescriptionSafety Shutdown
Position 12× 3/2-way CF-CServo-controlled, normally closed, with manual overrideStandard
Position 22× 3/2-way CF-CServo-controlled, normally closed, with manual overrideStandard
Position 32× 3/2-way CF-CServo-controlled, normally closed, with manual overrideStandard
Position 42× 3/2-way CF-CServo-controlled, normally closed, with manual overrideStandard
Position 52× 3/2-way CF-CServo-controlled, normally closed, with manual overrideStandard
Position 62× 3/2-way CF-CServo-controlled, normally closed, with manual overrideStandard
Position 72× 3/2-way CF-CServo-controlled, normally closed, with manual overrideStandard
Position 85/2-way monostable CF-HServo-controlled, single coil, port 1 pressurized to port 2 or 4SIA (External shut-off)
Position 95/2-way monostable CF-HServo-controlled, single coil, with manual overrideStandard
Position 105/2-way monostable CF-HServo-controlled, single coil, with manual overrideStandard
Position 115/2-way monostable CF-HServo-controlled, single coil, with manual overrideStandard
Position 122× 3/2-way CF-CServo-controlled, normally closedSIA (External shut-off)
Configuration ParameterFactory Setting for Article 20016285
Total Valve Slots12 PCE
Supply Connection MaterialBrass (Push-in connector D10 mm)
Working Port MaterialBrass (Push-in connector D6 mm)
AirLINE Quick Base MaterialAnodised aluminium
Auxiliary Pilot Air SupplyInternal
Left Additional Supply FeedPush-in connector D6 mm and D10 mm
Right / Middle Additional Supply FeedWithout (0 PCE intermediate feed)
Digital Input Electronic ModulesNot equipped (0 DI)
Integrated Check Valves in 3 (R) / 5 (S)No
Pneumatic HotSwap in 1 (P)No
Electrical Protection ClassIII according to DIN EN 61140, VDE 0140
Ingress Protection RatingIP20 (open), IP65 (in closed enclosure with AirLINE Quick)

Technical Data ​

Technical ParameterSpecification
Housing MaterialPolyamide (PA)
Seal MaterialsNBR and PUR
Station Width11 mm per valve slice
Maximum Controllable Valve FunctionsUp to 48 functions (24 slots max)
Operating Voltage24 V DC (±10%, residual ripple 1 Vss)
Nominal Power per Solenoid Valve0.7 W inrush (0.175 W holding after power reduction)
Nominal Current per Solenoid Valve29 mA inrush (10 mA holding after power reduction)
Flow Rate QNn Air310 l/min (measured at +20 °C, 6 bar inlet, 1 bar pressure drop)
Operating Pressure Range-1.00 bar to 10.00 bar (vacuum to 10 bar)
Pilot Air Pressure Range3.00 bar to 10.00 bar
Nominal Operating ModeContinuous operation (100% duty cycle ED)
Switching Time MeasurementMeasured according to ISO 12238 standard
Operating MediumOil-free or lubricated compressed dry air, neutral gases (5 µm filter recommended)
Compressed Air Quality ClassISO 8573-1:2010, Class 7.4.4
Ambient / Medium Temperature-10 °C to +55 °C
Storage Temperature-20 °C to +60 °C

AirLINE Quick Adapter System ​

The AirLINE Quick adapter plate allows direct structural assembly of the valve island into the cabinet floor or cabinet side wall cutout. Pneumatic working lines and exhaust channels pass directly through the cabinet boundary, eliminating bulkheads and internal piping.

BURKERT 20016285 (Type 8652) AirLINE Quick adapter plate for cabinet mounting

AirLINE Quick FeatureSpecification
Adapter Plate MaterialAnodised aluminium (Article 20016285) / Stainless steel 1.4301 optional
Pneumatic Fitting MaterialNickel-plated brass (Article 20016285) / Stainless steel 1.4401 optional
Supply / Exhaust Ports (P, R, S)Push-in connector D10 mm, 3/8"
Working Ports (2, 4)Push-in connector D6 mm, 1/4"
Mounting LocationControl cabinet floor or control cabinet side wall
Achievable Cabinet ProtectionIP65 according to EN 60529 / Type 4X (NEMA 250 with stainless steel variant)

Circuit Functions and SIA Safety Shut-Off ​

Article 20016285 combines standard Type 6534 solenoid valves with dedicated SIA variants on position 8 (CF-H) and position 12 (CF-C). SIA valves feature isolated pluggable electrical connections that route coil actuation through an external mechanical emergency shut-down contact or safety relay, independent of bus communication status.

BURKERT 20016285 (Type 8652) SIA safety shut-off wiring and terminal layout

Circuit Function CodeOperating PrincipleManual OverrideSIA Available
CF-C3/2-way solenoid valve, servo-controlled, normally closedLatching / spring returnYes (no manual override on SIA)
2× CF-CTwo 3/2-way solenoid valves on one station, normally closedLatching / spring returnYes (no manual override on SIA)
2× CF-DTwo 3/2-way solenoid valves on one station, normally openLatching / spring returnNo
CF-H5/2-way solenoid valve, servo-controlled, port 1 to 2 or 4Latching / spring returnYes (no manual override on SIA)
CF-Z5/2-way impulse solenoid valve with two coilsLatching / spring returnNo
CF-L5/3-way solenoid valve, middle position closedLatching / spring returnYes (no manual override on SIA)
CF-M5/3-way solenoid valve, middle position ventilatedLatching / spring returnNo
CF-N5/3-way solenoid valve, middle position exhaustedLatching / spring returnNo
SIA Technical SpecificationValue
Individual Valve SIA ConnectionPluggable screw-type terminal, 2-pin, coded, conductor cross-section 0.14–1.5 mm² (AWG 28–16)
Individual SIA Contact Switching Capacity0.5 A / 24 V DC (potential-free contact required)
Module-Based SIA ConnectionPluggable spring-loaded terminal, 12-pin, conductor cross-section 0.14–1.5 mm² (AWG 26–16)
Module SIA Contact Switching Capacity1.5 A / 24 V DC (potential-free contact required)

Factory Bridging on SIA Terminals

Upon delivery, the yellow SIA terminals are equipped with removable bridging clips. These clips enable direct operational testing and commissioning prior to routing the safety interlock loop. The bridging clips must be removed before wiring the external safety circuits.

Dimensions and Cabinet Mounting ​

Dimensions for 4-, 8-, and 12-slot variants are defined in standard millimetres. The 12-slot configuration of article 20016285 uses the dimensions listed below:

BURKERT 20016285 (Type 8652) dimensional drawing for 12-slot valve terminal

Terminal SizeDimension A (mm)Dimension B (mm)Cutout Fastening Holes Cmn
4-fold66—4× M531
8-fold351118× M572
12-fold (20016285)7715410× M5113

Standard rail mounting complies with EN 50022 (35 × 7.5 mm or 35 × 15 mm). When installing inside enclosures, maintain clearance from the front edge of the terminal to ensure accessibility for valve replacement.

Electrical and Communication Connections ​

The electrical architecture separates the control/communication power from the valve coil driving voltage. Power supply for communication and display is wired via a 5-pin spring-loaded terminal, whereas valve coils receive power through an independent 2-pin terminal.

Terminal TypePin / Wire ColourSignal AssignmentFunctional Description
5-Pin Spring Terminal (Control Power)Red24 V DCElectronics and display supply
5-Pin Spring TerminalWhiteCAN_HbüS local bus interface
5-Pin Spring TerminalGreenShieldCable shield grounding
5-Pin Spring TerminalBlueCAN_LbüS local bus interface
5-Pin Spring TerminalBlack0 V DC (GND)Reference ground
2-Pin Spring Terminal (Valve Power)Pin 1 (Red)AUX 24 V DCPneumatic valve coil supply
2-Pin Spring TerminalPin 2 (Black)0 V DC (GND)Valve ground reference

Industrial Ethernet communication connects via dual RJ45 ports (X1 and X2) supporting linear daisy-chain and ring network topologies.

BURKERT 20016285 (Type 8652) Industrial Ethernet dual RJ45 pin assignment

RJ45 PinIndustrial Ethernet SignalFunction
1TX+Transmit Data +
2TX-Transmit Data -
3RX+Receive Data +
4N.C.Not connected
5N.C.Not connected
6RX-Receive Data -
7N.C.Not connected
8N.C.Not connected

BURKERT 20016285 (Type 8652) Industrial Ethernet master and büS slave network architecture

In combined architectures, an Industrial Ethernet-equipped Type 8652 functions as a fieldbus master node, coordinating subordinate büS-equipped AirLINE islands in sub-networks.

Approvals, Conformities, and Hazardous Area Rules ​

Type 8652 valve islands comply with relevant European Directives and hold international explosion-protection certifications.

Certification Agency / DirectiveClassification / StandardDescription
ATEX (DEKRA BVS 20 ATEX E 031 U)II 3G Ex ec IIC Gc
II 3D Ex tc IIIC Dc
Category 3 device for Zone 2 (gas) and Zone 22 (dust)
IECEx (IECEx BVS 20.0024 U)Ex ec IIC Gc
Ex tc IIIC Dc
International explosion protection standard
UL Listed (USA / Canada)UL 61010-1
CAN/CSA-C22.2 No. 61010-1
Electrical safety for control and laboratory use
UL Recognized HazLoc (cURus)Class I, Zone 2, AEx ec IIC Gc
Class II, Zone 22, AEx tc IIIC Dc
Class I, Div 2, Gr A–D; Class II/III, Div 2, Gr F–G
Hazardous location certification for North America
CCC (China Compulsory Cert.)GB/T 3836.2021Certified by SITIIAS for explosive atmospheres in China
Enclosure RatingType 4X (NEMA 250)In closed cabinets with stainless steel AirLINE Quick plate

Hazardous Area Installation Conditions

When operating in potentially explosive environments (Zone 2 or Zone 22), the valve terminal must be mounted inside an approved enclosure with an ingress rating of at least IP54 for gas (3G/Gc) and IP64 or IP6X for dust (3D/Dc). Terminal blocks (24 V DC power, SIA, EVS, and digital inputs) may only be connected or disconnected when the electrical circuits are completely de-energized. Pneumatic Hot Swap valve replacement is prohibited while an explosive atmosphere is present unless the area is formally certified non-hazardous.

Replacement Valves and System Accessories ​

Replacement ItemDescriptionArticle No.
Type 6534 Standard Valve2× 3/2-way CF-C, 24 V DC, 270 l/min (with screw)301374
Type 6534 Standard Valve2× 3/2-way CF-D, 24 V DC, 310 l/min (with screw)301375
Type 6534 Standard Valve5/2-way CF-H, 24 V DC, 290 l/min (with screw)301376
Type 6534 Standard Valve5/2-way CF-Z impulse, 24 V DC, 290 l/min (with screw)301377
Type 6534 Standard Valve5/3-way CF-L closed center, 24 V DC, 275 l/min (with screw)301380
Type 6534 SIA Valve2× 3/2-way CF-C, 24 V DC, shutdown port (with screw)338802
Type 6534 SIA Valve5/2-way CF-H, 24 V DC, shutdown port (with screw)338805
Dummy Valve PlateBlanking plate for unpopulated valve slots335779
5-Pin Terminal PlugSpring-loaded terminal for communication/display power920180
2-Pin Terminal PlugSpring-loaded terminal for pneumatic valve AUX 24 V power920442
AirLINE Quick Screw Set10× M5 × 10 A2 DIN 6912 cabinet fastening screws308661
Height Adapter 12-SlotAirLINE Quick 12-slot height adapter (without intermediate feed)754961
Retaining Plate 12-SlotRetaining plate for exterior cabinet mounting (12-slot)60005567
Blind Plate 12-SlotCovering plate for 12-slot cutout754966
ME43 Gateway ModuleIndustrial Ethernet gateway (PROFINET, EtherNet/IP, Modbus TCP, EtherCAT)301799
USB büS Interface Set 1Type 8923 programming set for Bürkert Communicator software772426
Bürkert CommunicatorConfiguration and diagnosis software for EDIP devicesType 8920