Skip to content
SIMATIC ET 200SP / SP HAIP20 / IP65ATEX / IECExUL Listed

BURKERT 20065481 Type 8647 AirLINE SP Electropneumatic Valve Island

Burkert Type 8647 AirLINE SP valve island for direct integration into Siemens SIMATIC ET 200SP and ET 200SP HA. Features LC display and safety-related shut-off.

BURKERT 20065481 Type 8647 AirLINE SP Electropneumatic Valve Island

Burkert Type 8647 AirLINE SP pneumatic valve island is a modular, electropneumatic automation system consisting of connection and valve modules. It has been especially developed for safe and complete integration into the decentralised peripheral systems "SIMATIC ET 200SP" and "SIMATIC ET 200SP HA" from Siemens. Pneumatically operated process valves, pneumatic cylinders, or other pneumatic components can be connected to the pneumatic outputs.

If the pneumatic components are installed with position feedbacks, the position of the actuated pneumatic components can be displayed on the associated pilot valve. This can save time on start-up and maintenance. The valve block and the electronic modules of SIMATIC ET 200SP / SIMATIC ET 200SP HA provide numerous features, including extensive configuration options, diagnostics capabilities, and safety-related shut-off of valves.

Key Features

  • Direct connection to the I/O systems SIMATIC ET 200SP and SIMATIC ET 200SP HA
  • Integration in Siemens PCS7 possible
  • Siemens Product Partner for SIMATIC Automation Systems
  • Easy diagnostics by LC display
  • Safety-related shut-off of valves possible

General Technical Data

Product propertiesType 0460, Type 6524, Type 6525
MaterialBody: PA (polyamide), PC (polycarbonate) (valves: PA, PPS or aluminum)
Seal: NBR (valves: FPM, NBR and PUR)
Width per station11 mm
Manual overrideStandard
Number of valve slotsFor single valves: max. 64
For impulse and double valves: max. 32
Maximum valve functions64 on one valve block, several valve blocks possible on one station
Pressure rangeVacuum to 10 bar (with UL approval Vac to 8 bar)
Flow rate QNn value air200 to 300 l/min measured at + 20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure
Operating voltage24 V DC (±10 % tolerance)
Nominal power of each valveFor single valves: 0.8 W
For impulse and double valves: 2× 0.8 W with power reduction
Safety-related shut-offShut-off of individual valve via second connection
Module-based shut-off (EVS function)
Block-based shut-off (valve island) via Siemens F-PMe module
Operating mediumOil-free or lubricated compressed dry air (5 μm filter recommended)
Degree of protectionIP20, IP65 in closed control cabinets
Communication moduleSiemens SIMATIC ET 200SP / SP HA
Communication interfacePROFIBUS DP, PROFINET IO

System Overview

Combining modules from the distributed Siemens I/O systems SIMATIC ET 200SP/SP HA with the valve block AirLINE SP Type 8647 provides an integrated system of electronic and pneumatic components.

BURKERT 20065481 Burkert Type 8647 AirLINE SP valve block overview

Connection Units

The pneumatic supply and deaeration of the valve block occurs via connection units. Furthermore, the valve block is fixed to the standard rail via the connection units. Connection units can be optionally equipped with a pressure gauge or electronic pressure sensor. At the variant with electronic pressure sensor, the measured supply pressure is provided as an analog value via ET 200SP.

BURKERT 20065481 Burkert Type 8647 connection units overview

Valve Units

Valve units convert the electrical control signals of the interface module into pneumatic output signals and provide the pneumatic outputs. There are valve units with four valve slots (4-slot valve unit) or with eight valve slots (8-slot valve unit).

BURKERT 20065481 Burkert Type 8647 valve units overview

Solenoid Valves for Pneumatics

Type 6524 and Type 6525

The pilot valve Type 6524 (single and double valve) and Type 6525 (single valve) consist of a pilot flipper solenoid valve Type 6144 and a pneumatic seat valve. The circuit function allows switching of high pressures with low power consumption and short switching times. The pilot valves are equipped with a manual override as standard.

Type 0460

The solenoid valve Type 0460 consists of a pneumatic valve body fitted with a double coil pilot valve. The principle allows switching of high pressures together with low power consumption and fast switching times. All valves are equipped with manual override as a standard.

AirLINE Quick

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.

BURKERT 20065481 Burkert Type 8647 AirLINE Quick Adapter in stainless steel or anodised aluminium

Advantages:

  • Reduced space requirement in the control cabinet
  • This makes it possible to use more compact control cabinets
  • Reduced installation effort due to hose connections directly at the bottom of the control cabinet

Note

The valves of Type 0460 cannot be installed with AirLINE Quick due to their size.

Circuit Functions

Circuit functionDescription
C (CF C)3/2-way solenoid valve, Servo-controlled, with manual override, Normally closed
C (CF C)2 × 3/2-way solenoid valve, Servo-controlled, with manual override, Normally closed
D (CF D)3/2-way solenoid valve, Servo-controlled, with manual override, Normally open
H (CF H)5/2-way solenoid valve, Servo-controlled, with manual override, Pressure applied via port (1)
L (CF L)5/3-way solenoid valve, With manual override, In middle position all ports locked
N (CF N)5/3-way solenoid valve, With manual override, In middle position ports 2 and 4 exhausted
Z (CF Z)5/2-way solenoid valve, Impulse variant with 2 coils and manual override

Approvals and Conformities

  • Explosion protection: Optional as a category 3 device suitable for zone 2. ATEX: BVS 18 ATEX E 078 XII 3G Ex ec IIC T4 Gc. IECEx: IEC Ex BVS 18.0068 X Ex ec IIC T4 Gc.
  • North America (USA/Canada): Optional UL Listed for the USA and Canada according to UL 61010-1 and CAN/CSA-C22.2 No. 61010-1.

Installation Notes

  • External-Valve-Shut-off function (EVS function): the switching contact must be located in the same control cabinet as the valve block. The line length must be limited to a maximum of 2 m.
  • The Hot Swap function of the individual valves cannot be combined with the ATEX/IECEx-Ex approval.