Skip to content
SIMATIC ET 200SP CompatibleAirLINE QuickIP20 / IP65

BURKERT 20073576 8647 AirLINE SP Electropneumatic Automation System

Burkert Type 8647 AirLINE SP electropneumatic automation system. Modular valve island for direct integration into Siemens SIMATIC ET 200SP and ET 200SP HA.

BURKERT 20073576 8647 AirLINE SP Electropneumatic Automation System

Burkert Type 8647 AirLINE SP is a modular, electropneumatic automation system consisting of connection and valve modules. It has been especially developed for safe and complete integration into the decentralised peripheral system "SIMATIC ET 200SP" and "SIMATIC ET 200SP HA" from Siemens. Pneumatically operated process valves, pneumatic cylinders or other pneumatic components can be connected to the pneumatic outputs. If the pneumatic components are installed with position feedbacks, the position of the actuated pneumatic components can be displayed on the associated pilot valve. This can save time on start-up and maintenance.

BURKERT 20073576 Burkert 8647 AirLINE SP electropneumatic automation system overview

  • Direct connection to the I/O systems SIMATIC ET 200SP and SIMATIC ET 200SP HA
  • Integration in Siemens PCS7 possible
  • Siemens Product Partner for SIMATIC Automation Systems
  • Easy diagnostics by LC display
  • Safety-related shut-off of valves possible

System Overview

Combining modules from the distributed Siemens I/O systems SIMATIC ET 200SP/SP HA with the valve block AirLINE SP Type 8647 provides an integrated system of electronic and pneumatic components. Depending on the requirement, electrical and pneumatic modules with various functions can be combined with each other by the observation of simple rules.

BURKERT 20073576 Burkert 8647 valve block AirLINE SP system overview

The valve block is used to incorporate pneumatic pilot valves directly in SIMATIC ET 200SP/SP HA and to activate them via SIMATIC ET 200SP/SP HA. The valve block and the electronic modules of SIMATIC ET 200SP/SIMATIC ET 200SP HA provide numerous features, e.g. extensive configuration options or diagnostics capabilities. Optionally, valve groups can be switched off by an external, potential-free switching contact. It is then easy to implement control concepts, e.g. "Central system off".

General Technical Data

Product propertiesType 0460, Type 6524, Type 6525
Body materialPA (polyamide), PC (polycarbonate) (valves: PA, PPS or aluminum)
Seal materialNBR (valves: FPM, NBR and PUR)
Width per station11 mm
Manual overrideStandard
Number of valve slotsFor single valves: max. 64. For impulse and double valves: max. 32
Maximum number of valve functions64 on one valve block, several valve blocks possible on one station
Pressure rangeVac to 10 bar (with UL approval Vac to 8 bar)
Flow rate QNn value air200 to 300 l/min measured at + 20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure
Operating voltage24 V DC (±10 % tolerance)
Nominal power of each valveFor single valves: 0.8 W. For impulse and double valves: 2× 0.8 W with power reduction
Operating mediumOil-free or lubricated compressed dry air (5 μm filter recommended)
Degree of protectionIP20, IP65 in closed control cabinets
Working portD 6, D 1/4, ALQ
Air supply connectionG 1/4, D 3/8
Communication moduleSiemens SIMATIC ET 200SP / SP HA
Communication interfacePROFIBUS DP, PROFINET IO
Ambient temperature0 °C to + 55 °C (for valve Type 0460: 0 °C to + 50 °C)

Circuit Functions

SymbolDescription
C (CF C)3/2-way solenoid valve. Servo-controlled, with manual override. Normally closed.
C (CF C)2 × 3/2-way solenoid valve. Servo-controlled, with manual override. Normally closed.
D (CF D)3/2-way solenoid valve. Servo-controlled, with manual override. Normally open.
H (CF H)5/2-way solenoid valve. Servo-controlled, with manual override. Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure.
L (CF L)5/3-way solenoid valve. With manual override. In middle position all ports locked.
N (CF N)5/3-way solenoid valve. With manual override. In middle position ports 2 and 4 exhausted.
Z (CF Z)5/2-way solenoid valve. Impulse variant with 2 coils and manual override. Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure.

AirLINE Quick

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.

BURKERT 20073576 Burkert 8647 AirLINE Quick adapter in stainless steel or anodised aluminium

Advantages:

  • Reduced space requirement in the control cabinet
  • This makes it possible to use more compact control cabinets
  • Reduced installation effort due to hose connections directly at the bottom of the control cabinet

Note

The valves of Type 0460 valves cannot be installed with AirLINE Quick due to their size.

Approvals and Conformities

  • Explosion protection: Optional: Explosion protection. As a category 3 device suitable for zone 2. ATEX: BVS 18 ATEX E 078 XII 3G Ex ec IIC T4 Gc. IECEx: IEC Ex BVS 18.0068 X Ex ec IIC T4 Gc.
  • North America (USA/Canada): Optional: UL Listed for the USA and Canada. The products are UL Listed for the USA and Canada according to: UL 61010-1 and CAN/CSA-C22.2 No. 61010-1.

DANGER

The electrical shutdown of valve Types 6524 and 6525 causes them to return to the rest position. The selection of the appropriate circuit function of the valve (CFC, CFD or CFH) depends on the application and is the responsibility of the user. To avoid brief back pressures in the event of a safety shutdown, the use of valve blocks with integrated check valves is strongly recommended. Using manual override to operate valves overrides the electrical shutdown.

If a valve block Type 8647 is operated in the potential group of an F-PM-E 24VDC/8A PPM ST power module of the ET 200SP, the load voltage of the valve block can be shut down by the power module for safety reasons. Valves of Types 6524 and 6525 return to their rest position. The prerequisite for safe operation is that the electrical supply of the valve block is provided by a SELV/PELV power supply unit.