BURKERT 20081087 Type 8652 AirLINE 16-slot valve island features an aluminium AirLINE Quick base, Industrial Ethernet RJ45 connectivity, 13 pre-installed 2x3/2 CF-C valves, and IP20 rating.

BURKERT 20081087 Type 8652 AirLINE is a 16-slot electro-pneumatic valve island engineered for process automation environments, pre-configured with 13 dual 3/2-way normally closed valves (CF-C) and 3 blind plates on an AirLINE Quick anodised aluminium base. The system integrates an ME43 fieldbus gateway supporting Industrial Ethernet protocols (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic) via dual RJ45 ports. Operating from a 24 V DC supply across a pressure range of -1 bar to 10 bar, the unit provides a nominal air flow rate of 310 l/min per valve station at 6 bar inlet pressure and 1 bar differential pressure.

| Product Property | Technical Data |
|---|---|
| Valve Island Type | Type 8652 AirLINE (Article 20081087) |
| Body Material | Polyamide (PA) |
| Seal Material | NBR and PUR |
| Number of Valve Slots | 16 slots (configured: 13x 2x 3/2-way CF-C, 3x blind plates) |
| Width per Station | 11 mm |
| Manual Override | Latching, spring return (optional lockable) |
| Pneumatic Intermediate Supply | 1 intermediate supply module included (standard on 16-, 20-, and 24-slot variants) |
| Nominal Operating Pressure | -1.00 bar to 10.00 bar (vacuum to 10 bar) |
| Auxiliary Pilot Air | 3 bar to 10 bar (internal feed configured) |
| Nominal Flow Rate QNn (Air) | 310 l/min (measured at +20 °C, 6 bar inlet pressure, 1 bar pressure drop) |
| Flow Rate with Hot Swap Active | Flow reduced by approximately 3% |
| Operating Mode | Continuous operation (100% duty cycle) |
| Switching Time Measurement | According to ISO 12238 |
| Operating Voltage | 24 V DC (±10%), residual ripple 1 Vss |
| Nominal Power per Valve | 0.7 W (0.175 W after power reduction) |
| Nominal Current per Valve | 29 mA (10 mA after power reduction) |
| Digital Inputs | 0 (basic version without display or input modules) |
| Protection Class | Class III according to DIN EN 61140, VDE 0140 |
| Operating Medium | Oil-free or lubricated compressed dry air, neutral gases (5 µm filter recommended) |
| Compressed Air Quality | ISO 8573-1:2010, Class 7.4.4 |
| Degree of Protection | IP20 (bare unit); IP65 when mounted in closed control cabinet with AirLINE Quick |
| Storage Temperature | -20 °C to +60 °C |
| Medium and Ambient Temperature | -10 °C to +55 °C |

AirLINE Quick enables direct mechanical mounting of the valve terminal onto the control cabinet floor or wall, eliminating separate bulkhead connections and internal tubing runs.
| Property | Specification |
|---|---|
| Adapter Plate Material | Anodised aluminium (Article 20081087 configuration; optional 1.4301 stainless steel) |
| Pneumatic Connector Material | Nickel-plated brass (optional 1.4401 stainless steel) |
| Pneumatic Supply / Exhaust Ports (1, 3, 5) | Push-in connector D10 mm, 3/8" |
| Pneumatic Working Ports (2, 4) | Push-in connector D6 mm, 1/4" |
| Mounting Position | Control cabinet floor or control cabinet wall |
The 20081087 unit is pre-assembled with 16 valve slots allocated as follows:
Type 8652 accommodates multiple standard and safety-related valve circuit functions using Type 6534 sub-base solenoid valves:
| Circuit Function | Description |
|---|---|
| CF C (Single) | 3/2-way solenoid valve, servo-controlled, with manual override, normally closed |
| CF C (Dual) | 2x 3/2-way solenoid valve, servo-controlled, with manual override, normally closed |
| CF D (Dual) | 2x 3/2-way solenoid valve, servo-controlled, with manual override, normally open |
| CF H | 5/2-way solenoid valve, servo-controlled, with manual override; pressure applied via port 1 feeds port 2 or 4 |
| CF L | 5/3-way solenoid valve, servo-controlled, with manual override; all ports locked in middle position |
| CF M | 5/3-way solenoid valve, servo-controlled, with manual override; ports 2 and 4 pressurized in middle position |
| CF N | 5/3-way solenoid valve, servo-controlled, with manual override; ports 2 and 4 exhausted in middle position |
| CF Z | 5/2-way solenoid valve, impulse variant with 2 coils and manual override |
| SIA CF C | Safety-related 3/2-way or 2x 3/2-way valve without manual override, with external shutdown terminal |
| SIA CF H | Safety-related 5/2-way valve without manual override, with external shutdown terminal |
| SIA CF L | Safety-related 5/3-way valve without manual override, all ports locked in middle position |
Type 8652 holds certifications for international industrial installations and hazardous location categories:
Hazardous Location Operating Restrictions

Dimensional layout for Type 8652 valve islands with 16, 20, and 24 valve slots (all dimensions in mm):
| Variant | A | B | C | D | m | m' | n |
|---|---|---|---|---|---|---|---|
| 16-fold with intermediate supply (20081087) | 112 | 224 | 10x M5 | 114.3 | 7 | 7 | 4 |
| 20-fold with intermediate supply | 134 | 268 | 10x M5 | 158.3 | 11 | 7 | 5 |
| 24-fold with intermediate supply | 156 | 312 | 10x M5 | 158.3 | 11 | 11 | 6 |
| 16-fold without intermediate supply | 99 | 198 | 10x M5 | — | 15 | — | 4 |
| 20-fold without intermediate supply | 121 | 242 | 10x M5 | — | 19 | — | 5 |
| 24-fold without intermediate supply | 143 | 286 | 10x M5 | — | 23 | — | 6 |
Installation Clearance for Hot Swap
When mounting the valve island inside a control cabinet, maintain sufficient clearance between the valve island front and the cabinet door/front edge to permit unhindered insertion and removal of valve bodies during maintenance. Observe the specified rear-wall-to-mounting-plate spacing.
Type 8652 separates electronic communications power from pneumatic valve actuation power via independent terminal blocks.
| Pin | Wire Colour | Assignment |
|---|---|---|
| 1 | Red | 24 V DC |
| 2 | White | CAN_H (büS connection) |
| 3 | Green | Shielding |
| 4 | Blue | CAN_L (büS connection) |
| 5 | Black | GND (0 V DC) |
| Clip | Wire Colour | Assignment |
|---|---|---|
| 1 | Red | AUX 24 V |
| 2 | Black | GND (0 V DC) |

Article 20081087 includes an ME43 Industrial Ethernet gateway with dual RJ45 Ethernet ports (X1 and X2) supporting PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic:
| Pin | Assignment |
|---|---|
| 1 | TX+ |
| 2 | TX- |
| 3 | RX+ |
| 4 | Not connected (N.C.) |
| 5 | Not connected (N.C.) |
| 6 | RX- |
| 7 | Not connected (N.C.) |
| 8 | Not connected (N.C.) |

Article 20081087 is built with a standard 24 V interface plate without modular shut-off. Modular configurations within Type 8652 accommodate optional electronic sub-modules:
Type 8652 supports up to 48 digital inputs across modular stations. Each input is supplied with 24 V DC, current-limited to 30 mA, accepting 2-wire, 3-wire, or dry contact mechanical switches.
| Property | Value |
|---|---|
| Diagnostics | Open-circuit detection (2-wire sensors), short-circuit detection (3-wire sensors) |
| Switching Threshold | V_OFF = 0 to 5 V; V_ON = 10 to 30 V |
| Input Current at V_ON | Max. 5.7 mA per channel (typical at 24 V DC) |
| Input Impedance | > 4 kΩ |
| Galvanic Isolation | No, common reference potential for all channels |
| Maximum Cable Length | < 30 m (cross-section ≤ 1.5 mm²) |
For functional safety architectures, Type 6534 SIA replacement valves integrate dedicated terminal blocks to cut coil power independently of fieldbus commands via external potential-free contacts. Alternatively, a 12-pin spring-loaded terminal module provides group-based emergency shut-off with contact switching ratings up to 1.5 A at 24 V DC.

An AirLINE Type 8652 valve island equipped with an Industrial Ethernet interface functions as an intelligent master valve terminal. Downstream sub-networks of Type 8652 islands fitted with büS interfaces connect as slave terminals via CANopen-based büS links, consolidating fieldbus nodes into a single Ethernet IP address.

Configuration and diagnostics are carried out through the Bürkert Communicator software (Type 8920), which operates on the EDIP (Efficient Device Integration Platform) framework.
All replacement valves include mounting screws and operate at 24 V DC with a 4 mm nominal orifice across vacuum to 10 bar (minimum 3 bar pilot pressure):
| Circuit Function | QNn (Air) | Opening Time | Closing Time | Article No. (Valve) | Article No. (Spare Kit) |
|---|---|---|---|---|---|
| CF C (Single 3/2-way NC) | 270 l/min | 15 ms | 15 ms | 20102334 | 20088974 |
| CF C (Dual 2x 3/2-way NC) | 270 l/min | 15 ms | 15 ms | 301374 | 296031 |
| CF D (Dual 2x 3/2-way NO) | 310 l/min | 15 ms | 15 ms | 301375 | 296032 |
| CF H (5/2-way) | 290 l/min | 20 ms | 25 ms | 301376 | 296033 |
| CF Z (5/2-way impulse, 2 coils) | 290 l/min | 20 ms | 25 ms | 301377 | 296034 |
| CF L (5/3-way, middle locked) | 275 l/min | 15 ms | 15 ms | 301380 | 296036 |
| CF M (5/3-way, middle vented) | 300 l/min | 20 ms | 20 ms | 301379 | 296035 |
| CF N (5/3-way, middle exhausted) | 300 l/min | 20 ms | 20 ms | 301381 | 296039 |
| Dummy Valve (Blind Plate) | — | — | — | 335779 | 327614 |
| Description | Variant | Quantity | Article No. |
|---|---|---|---|
| M5 x 10 A2 DIN 6912 Fastening Screws | Control cabinet base mounting | 10 | 308661 |
| Height Adapter | 16-fold with intermediate feed | 1 | 754962 |
| Height Adapter | 16-fold without intermediate feed | 1 | 60041928 |
| Retaining Plate (Cabinet Exterior) | 16-fold with intermediate feed | 1 | 60005568 |
| Retaining Plate (Cabinet Exterior) | 16-fold without intermediate feed | 1 | 60005880 |
| Blind Plate | 16-fold with intermediate feed | 1 | 754967 |
| Blind Plate | 16-fold without intermediate feed | 1 | 60041929 |
| Description | Article No. |
|---|---|
| ME43 Fieldbus Gateway — Industrial Ethernet (PROFINET, EtherNet/IP, Modbus TCP, EtherCAT) | 301799 |
| ME43 Fieldbus Gateway — PROFIBUS DP | 301803 |
| ME43 Fieldbus Gateway — CANopen / büS | 301802 |
| ME43 Fieldbus Gateway — PROFINET S2 | 20081296 |
| 5-Pin Spring-Loaded Terminal (Power & büS) | 920180 |
| 2-Pin Spring-Loaded Terminal (Valve 24 V Power) | 920442 |
| USB büS Interface Set 1 (Type 8923) for Bürkert Communicator | 772426 |
Explore similar products in our catalog