BURKERT 20081380 Type 8652 Valve Island, 20-Bank, Industrial Ethernet

BURKERT 20081380 Type 8652 AirLINE valve island. 20-bank configuration with Industrial Ethernet, AirLINE Quick aluminium adapter, and IP20 protection for process automation.

BURKERT 20081380 Type 8652 Valve Island, 20-Bank, Industrial Ethernet

BURKERT 20081380 Type 8652 AirLINE valve island is especially developed for process automation requirements. This specific model features a 20-bank configuration (20 PCE) with an Industrial Ethernet interface supporting PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic. It is equipped with an aluminium AirLINE Quick adapter plate, D3/8 brass pressure ports, and D 1/4 brass working ports. The hardware is optimised for installation at the bottom of the control cabinet, and key pneumatic functions ensure increased process reliability, such as check valves in the exhaust air ducts to prevent unplanned actuation due to pressure peaks.

BURKERT 20081380 Type 8652 AirLINE valve island overview

General Technical Data

Product propertiesDescription
Body MaterialPA (polyamide)
Seal MaterialNBR and PUR
Width per station11 mm
Number of valve slotsMax. 24 (Model 20081380 features 20 slots)
Pressure rangeVac to 10 bar (Nominal: -1 to 10 bar)
External supply air3 to 10 bar
Flow rate QNn value air310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure)
Operating voltage24 V DC (±10% tolerance)
Nominal power per valve0.7 W (0.175 W after power reduction)
Operating mediumOil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended)
Ambient temperature-10 °C to +55 °C
Degree of protectionIP20 (IP65 in closed control cabinets)

AirLINE Quick

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.

Advantages:

  • Reduced space requirement in the control cabinet
  • Makes it possible to use more compact control cabinets
  • Reduced installation effort due to hose connections directly at the bottom of the control cabinet

BURKERT 20081380 Type 8652 AirLINE Quick adapter plate

Circuit Functions

The Type 8652 supports various standard circuit functions, including:

  • Circuit function C (CF C): 3/2-way solenoid valve, servo-controlled, normally closed.
  • Circuit function D (CF D): 2 × 3/2-way solenoid valve, servo-controlled, normally open.
  • Circuit function H (CF H): 5/2-way solenoid valve, servo-controlled.
  • Circuit function L (CF L): 5/3-way solenoid valve, in middle position all ports locked.
  • Circuit function M (CF M): 5/3-way solenoid valve, in middle position ports 2 and 4 ventilated.
  • Circuit function N (CF N): 5/3-way solenoid valve, in middle position ports 2 and 4 exhausted.
  • Circuit function Z (CF Z): 5/2-way solenoid valve, impulse variant with 2 coils.

Approvals and Conformities

  • Explosion protection: Optional ATEX/IECEx Zone 2 (II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc).
  • North America: Optional UL Listed (UL 61010-1) and UL Recognized for Hazardous Locations (Class I, Zone 2; Class II, Zone 22; Class I, Div 2).
  • Others: China Compulsory Certification (CCC) for hazardous applications.

Dimensions (16-, 20- and 24-fold Variants)

BURKERT 20081380 Type 8652 dimensions for 16, 20, and 24-fold variants

VariantABCDmm'n
16-fold with intermediate supply11222410 x M5114.3774
20-fold with intermediate supply13426810 x M5158.31175
24-fold with intermediate supply15631210 x M5158.311116

Product Connections

Industrial Ethernet Interface

For the Industrial Ethernet variant (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic), the RJ45 interface (X1 and X2) pin assignment is as follows:

BURKERT 20081380 Type 8652 Industrial Ethernet RJ45 pin assignment

PinAssignment
1TX+
2TX-
3RX+
4N.C.
5N.C.
6RX-
7N.C.
8N.C.

Product Installation

To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.

BURKERT 20081380 Type 8652 installation inside control cabinet

Example Configuration

The following illustration shows a network with the example of AirLINE Type 8652 with Industrial Ethernet variant as master valve terminal and various AirLINE Type 8652 with büS variant as slave valve terminals.

BURKERT 20081380 Type 8652 example network configuration

Safety Instructions for Potentially Explosive Areas

When using Bürkert devices with codes PU17 or PX68 in potentially explosive areas, observe the following:

  • Danger from voltage: Disconnect the power supply before working on the device or system. Prevent unintentional reactivation.
  • Hot Swap: The use of the Hot Swap function is prohibited in a present explosive atmosphere. If it can be proven and ensured by means of suitable test equipment that there is no explosive atmosphere for a certain period of time, it is permissible to remove/insert valves using Hot Swap during this period.
  • Electrostatic charge: Take appropriate measures to ensure that no electrostatic charge can occur in the potentially explosive area. Clean the device surface by gently wiping it with a damp or antistatic cloth only.