BURKERT 20135392 Type 8652 12-Slot AirLINE Valve Island, Industrial Ethernet, AirLINE Quick AL

BURKERT 20135392 Type 8652 AirLINE 12-slot valve island integrates Industrial Ethernet, AirLINE Quick aluminium adapter plate, HotSwap in port P, and 12th slot SIA safety shut-off.

BURKERT 20135392 Type 8652 12-Slot AirLINE Valve Island, Industrial Ethernet, AirLINE Quick AL

BURKERT 20135392 Type 8652 AirLINE is a preconfigured 12-slot pneumatic valve island developed specifically for process automation installations. Equipped with an integrated ME43 Industrial Ethernet communication interface supporting PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic over dual RJ45 ports, the terminal provides direct process control and comprehensive diagnostics on an LC display as clear text and symbols. Diagnostics are also transmitted cyclically to the higher-level PLC to accelerate commissioning and fault tracking.

BURKERT 20135392 Type 8652 AirLINE valve terminal overview

The 20135392 configuration is assembled on an AirLINE Quick anodised aluminium baseplate for direct mounting to the floor or wall of a control cabinet. It features brass push-in connectors (D10 supply port, D6 working ports), internal auxiliary pilot air supply, and an auxiliary left threaded feed (G 1/4" and M7). The valve bank includes 11 standard stations with 2x 3/2-way normally closed valves and a 12th station equipped with a Type 6534 SIA safety shut-off valve with potential-free shutdown contacts, controlling up to 24 independent pneumatic paths.

Configuration of Model 20135392 ​

Model 20135392 provides a factory-assembled pneumatic and electronic configuration tailored for high-density cabinet installations:

Specification ParameterValue / Configuration
Article Number20135392
Terminal Type8652 AirLINE
Total Valve Slots12 slots (PCE)
Valve Positions 1 to 112x 3/2-way Circuit Function C (normally closed)
Valve Position 122x 3/2-way Circuit Function C SIA (safety shut-off variant)
Fieldbus CommunicationIndustrial Ethernet (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic)
Physical InterfaceDual RJ45 ports (X1 and X2)
Supply Connection (P)Push-in D10 mm, Brass
Working Ports (A, B)Push-in D6 mm, Brass
Baseplate InterfaceAirLINE Quick, Anodised Aluminium
Pilot Air ConfigurationInternal auxiliary pilot air
Left Additional SupplyThreaded ports G 1/4" and M7
Right / Middle SupplyWithout additional feed (0 intermediate supply modules)
Digital Input Modules0 DI (none fitted)
Exhaust Check ValvesIntegrated check valves in ports 3 (R) and 5 (S)
HotSwap FunctionIntegrated pneumatic HotSwap in supply port 1 (P)

Technical Specifications ​

Type 8652 operates continuously (100% duty cycle) across standard compressed air networks, conforming to ISO 8573-1:2010 Class 7.4.4 air quality.

Feature GroupParameterSpecification Value
MaterialsBodyPolyamide (PA)
SealsNBR and PUR
Width per Station11 mm
Pneumatic DataOperating Pressure Range-1.00 bar to 10.00 bar (Vacuum to 10 bar)
Auxiliary Pilot Air Pressure3 bar to 10 bar
Nominal Flow Rate QNn (Air)270 l/min (2x 3/2-way CF-C, measured at +20 °C, 6 bar inlet, 1 bar Δp)
HotSwap Flow ImpactFlow reduced by approx. 3%
Switching Times (ISO 12238)Opening: 15 ms; Closing: 15 ms
Manual OverrideLatching / spring return (standard valves)
Electrical DataOperating Voltage24 V DC (±10%, residual ripple 1 Vss)
Nominal Power per Valve0.7 W (drops to 0.175 W after electronic power reduction)
Nominal Current per Valve29 mA (drops to 10 mA after power reduction)
Protection ClassClass III according to DIN EN 61140, VDE 0140
EnvironmentAmbient Temperature Range-10 °C to +55 °C
Storage Temperature Range-20 °C to +60 °C
Operating MediumLubricated or oil-free compressed dry air, neutral gases (5 µm filter recommended)
Degree of ProtectionIP20 (standalone); IP65 in closed cabinet with AirLINE Quick

AirLINE Quick Adapter Plate ​

The AirLINE Quick system allows the valve terminal to mount directly onto the floor or wall of a control cabinet, leading pneumatic tubing straight through the enclosure cutout. This layout eliminates intermediate bulkheads and internal tubing runs, allowing significantly smaller cabinet enclosures.

BURKERT 20135392 AirLINE Quick anodised aluminium adapter plate

Component / FeatureSpecification Details
Adapter Plate MaterialAnodised aluminium (also available in stainless steel 1.4301)
Pneumatic Fitting MaterialNickel-plated brass (stainless steel 1.4401 optional)
Pneumatic Supply / Exhaust PortsPush-in connector D10 mm (3/8")
Pneumatic Working PortsPush-in connector D6 mm (1/4")
Mounting PositionControl cabinet floor or cabinet wall

Dimensions and Cabinet Mounting ​

For a 12-slot valve terminal, external dimensions follow standardized Burkert pitch dimensions. Mounting is supported directly onto the cabinet wall, cabinet floor cutout, or standard DIN rails EN 50022 (35 x 7.5 mm or 35 x 15 mm).

BURKERT 20135392 Type 8652 12-slot dimensional drawing

Terminal SizeDimension A (mm)Dimension B (mm)Mounting Screws CPitch Index mSpacing Index n
4-fold66—4 x M531
8-fold351118 x M572
12-fold (20135392)7715410 x M5113

Electrical and Fieldbus Connections ​

The valve terminal provides galvanic and electrical separation between the communication electronics and the pneumatic coil power circuits. Both power feeds must be supplied independently.

Communication and Display Power Supply ​

Power supply to the display and fieldbus communication module is wired through a 5-pin spring-loaded terminal block (wire cross-section ≤ 1.5 mm²):

Pin PositionTerminal ColourFunction / Assignment
1Red24 V DC
2WhiteCAN_H (büS connection)
3GreenShielding
4BlueCAN_L (büS connection)
5Black0 V DC (GND)

Pneumatic Valve Power Supply ​

Pneumatic valve coils receive power via a dedicated 2-pin spring-loaded terminal on the interface plate:

Terminal ClipTerminal ColourFunction / Assignment
1RedAUX 24 V DC
2Black0 V DC (GND)

Industrial Ethernet Interface (X1 and X2) ​

Dual RJ45 sockets support daisy-chain topology and ring redundancy protocols across Industrial Ethernet standards:

BURKERT 20135392 Industrial Ethernet RJ45 communication ports X1 and X2

RJ45 PinSignal AssignmentDescription
1TX+Transmit Data +
2TX-Transmit Data -
3RX+Receive Data +
4N.C.Not connected
5N.C.Not connected
6RX-Receive Data -
7N.C.Not connected
8N.C.Not connected

Cabinet Installation and HotSwap Clearance ​

Type 8652 includes pneumatic HotSwap in supply port 1 (P), allowing individual pilot valves to be replaced under full line pressure without shutting down adjacent actuators or bleeding the main air line. Check valves built into exhaust channels 3 (R) and 5 (S) prevent reverse pressure surges from inadvertently moving single-acting cylinders.

BURKERT 20135392 control cabinet installation and HotSwap clearance

HotSwap Maintenance Distance

To safely insert and release individual valve slices using the HotSwap mechanism, adhere to the minimum spacing between the terminal body and the front edge or doors of the control cabinet as defined in the Type 8652 operating instructions.

Safety Shutdown (SIA) and Circuit Functions ​

Position 12 on model 20135392 is fitted with a Type 6534 SIA variant valve. While slots 1 to 11 use standard 2x 3/2-way normally closed valves with manual overrides, the SIA variant features dedicated electrical terminal connections to interrupt the coil circuit externally via emergency contacts or safety relays, completely bypassing bus communication.

BURKERT 20135392 Type 6534 SIA safety-related shut-off valve terminal

FeatureSIA Safety Shutdown Specification
Terminal TypePluggable screw-type terminal, 2-pin, mechanically coded
Conductor Cross-Section0.14 mm² to 1.5 mm² (AWG 28–16), rigid or flexible
Contact Switching Capacity0.5 A at 24 V DC
Manual OverrideNone (manual operation omitted on SIA versions)
Delivery ConditionFitted with removable bypass bridge for immediate commissioning
External Contact TypePotential-free contact (mechanical safety switch or safety relay)

Network Topology Example ​

Type 8652 with Industrial Ethernet acts as a fieldbus master gateway that coordinates pneumatic sub-stations across an automation cell. Downstream Bürkert büS valve islands can be integrated into the network topology as slaves.

BURKERT 20135392 Industrial Ethernet master network configuration diagram

Configuration, parameterization, and diagnostic logging are executed using the Bürkert Communicator software (Type 8920) on the EDIP platform via a PC-linked USB-büS interface adapter.

Replacement Valves and Accessories ​

Individual valve slices, connectors, and mounting hardware can be ordered as replacement units or expansions:

Type 6534 Replacement Pilot Valves ​

Circuit FunctionWidthPressure RangeFlow Rate QNnVoltageArticle No. (incl. screws)
2x 3/2-way CF-C Standard (Manual override, NC)11 mmVac. to 10 bar270 l/min24 V DC301374 (REF 296031)
2x 3/2-way CF-C SIA (External shut-off, NC)11 mmVac. to 10 bar270 l/min24 V DC338802 (REF 336443)
Dummy Valve Plate11 mm———335779 (REF 327614)

Terminal Plugs and Fieldbus Modules ​

Component DescriptionWiring DetailsArticle No.
5-Pin Spring-Loaded Terminal BlockCommunication & display power supply920180
2-Pin Spring-Loaded Terminal BlockPneumatic valve coil power supply920442
ME43 Gateway ModuleIndustrial Ethernet (PROFINET, EtherNet/IP, Modbus TCP, EtherCAT)301799

12-Slot AirLINE Quick Accessories ​

Accessory ItemSpecification / ApplicationQuantityArticle No.
Fastening Screw SetM5 x 10 A2 DIN 6912 (fastening to cabinet base)10 pcs308661
Height Adapter Plate12-fold, without intermediate supply1 pc754961
Retaining Plate12-fold, for cabinet exterior mounting1 pc60005567
Blind Cover Plate12-fold, without intermediate supply1 pc754966

Hazardous Location Operating Conditions ​

When specified for potentially explosive atmospheres under codes PU17 or PX68, Type 8652 conforms to international explosion-protection certifications:

  • ATEX: BVS 20 ATEX E 031 U — II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc
  • IECEx: IECEx BVS 20.0024 U — Ex ec IIC Gc / Ex tc IIIC Dc
  • CCC: Certified according to GB/T 3836 series standards for hazardous areas in China
  • cURus HazLoc (USA/Canada): Class I, Zone 2, AEx ec IIC Gc; Class II, Zone 22, AEx tc IIIC Dc; Class I, Division 2, Groups A, B, C, D; Class II/III, Division 2, Groups F, G

Potentially Explosive Atmosphere Precautions

Terminal blocks for 24 V power, SIA shutdown, and digital inputs must only be connected or disconnected in an unpowered state when an explosive atmosphere is present. Pneumatic HotSwap must not be performed in hazardous locations unless the area is verified to be non-explosive using calibrated test equipment. For Zone 2 (3G) installations, the cabinet enclosure must provide at least IP54 ingress protection; for Zone 22 (3D), at least IP6X is required.