Burkert 20136339 (Type 8652) is a 20-slot AirLINE Quick valve island with stainless steel adapter plate, 20x 3/2-way CF-C valves, 40 digital inputs, PROFIBUS DPV1 interface, and pneumatic HotSwap in port 1.

BURKERT 20136339 (Type 8652) is an electro-pneumatic valve island configured with a 20-slot AirLINE Quick stainless steel base, designed for process automation environments. All 20 valve stations are fitted with Type 6534 servo-controlled 3/2-way solenoid valves in circuit function C (normally closed), providing independent actuation for single-acting pneumatic actuators and process valves. The island communicates via PROFIBUS DPV1 using a standard Sub-D 9-pin interface and integrates 5 electronic input modules providing 40 digital inputs for direct field limit-switch and sensor feedback.
Pneumatic reliability is supported by integrated check valves in the exhaust ducts 3 (R) and 5 (S), which stop backpressure surges from causing accidental valve actuation. The island includes a pneumatic HotSwap function at supply port 1 (P), allowing individual pilot valves to be replaced during live plant operation with only an approximate 3% flow reduction. Process connections feature a stainless steel D10 mm push-in main supply port and stainless steel D6 mm push-in working ports, supplemented on the left module by threaded G 1/4" and M7 ports.
| Specification Parameter | Technical Value |
|---|---|
| Model & Article Number | Type 8652 / SKU 20136339 |
| Total Valve Slots | 20 slots (stations 1 through 20: 3/2-way CF-C) |
| Valve Width per Station | 11 mm |
| Communication Interface | PROFIBUS DPV1 via ME43 gateway (Sub-D 9-pin female) |
| Digital Input Capacity | 40 DI (5 modules x 8 inputs per module) |
| Base Plate Execution | AirLINE Quick stainless steel 1.4301 |
| Supply Port 1 (P) | Push-in fitting D10 mm (stainless steel 1.4401) |
| Working Ports 2 / 4 | Push-in fitting D6 mm (stainless steel 1.4401) |
| Additional Air Supply | Left: G 1/4" and M7; Right: none; Middle: none (0 PCE) |
| Pilot Air Configuration | Internal auxiliary pilot air |
| Operating Pressure Range | -1.00 bar to 10.00 bar (vacuum to 10 bar) |
| Pilot Pressure Range | 3.00 bar to 10.00 bar |
| Rated Flow Rate QNn (Air) | 270 l/min per CF-C valve (reference: 310 l/min at 6 bar inlet, 1 bar ΔP) |
| Operating Voltage | 24 V DC (±10%, residual ripple 1 Vss) |
| Nominal Power per Coil | 0.7 W (0.175 W after internal holding current drop) |
| Nominal Current per Coil | 29 mA (10 mA after power reduction) |
| Degree of Protection | IP20 bare; IP65 when mounted through closed enclosure wall |
| Enclosure Rating | NEMA 250 Type 4X in closed enclosures (stainless steel variant) |
| Ambient & Medium Temperature | -10 °C to +55 °C (Storage: -20 °C to +60 °C) |

AirLINE Quick allows the valve island to mount directly into the cutout of a control cabinet floor or wall, eliminating bulkheads, separate pass-throughs, and internal cabinet tubing. Burkert 20136339 utilizes a mechanical adapter plate made of stainless steel 1.4301 equipped with stainless steel 1.4401 push-in connectors. Working lines route outside the enclosure, protecting sensitive electronics from process-side hose stress.
| Feature | AirLINE Quick Specification |
|---|---|
| Adapter Plate Material | Stainless steel 1.4301 |
| Pneumatic Port Fitting Material | Stainless steel 1.4401 |
| Pneumatic Supply / Exhaust (Ports 1, 3, 5) | Push-in fitting D10 mm (optional 3/8") |
| Pneumatic Working Ports (Ports 2, 4) | Push-in fitting D6 mm (optional 1/4") |
| Installation Position | Control cabinet floor or control cabinet wall |
| Achieved Enclosure Ingress Protection | IP65 according to EN 60529 in closed control cabinet |

Burkert 20136339 is configured without an intermediate supply module (0 PCE intermediate feed). Dimensions in mm are specified in the engineering table below for 16-, 20-, and 24-slot variants:
| Configuration Variant | A [mm] | B [mm] | C [Holes] | D [mm] | m [mm] | m' [mm] | n [Slots] |
|---|---|---|---|---|---|---|---|
| 16-fold with intermediate supply | 112 | 224 | 10 x M5 | 114.3 | 7 | 7 | 4 |
| 20-fold with intermediate supply | 134 | 268 | 10 x M5 | 158.3 | 11 | 7 | 5 |
| 24-fold with intermediate supply | 156 | 312 | 10 x M5 | 158.3 | 11 | 11 | 6 |
| 16-fold without intermediate supply | 99 | 198 | 10 x M5 | — | 15 | — | 4 |
| 20-fold without intermediate supply (20136339) | 121 | 242 | 10 x M5 | — | 19 | — | 5 |
| 24-fold without intermediate supply | 143 | 286 | 10 x M5 | — | 23 | — | 6 |
Power supply and communication lines are routed through separate terminal connections on the interface plate to keep pneumatic coil switching currents isolated from the logic bus.

| Pin Number | Assignment | Description |
|---|---|---|
| Pin 1 | SHIELDING | Cable shield / protective ground |
| Pin 2 | M24 (optional) | Return line 24 V DC ground |
| Pin 3 | RxD/TxD-P (B-line) | Receive / transmit data positive (red core) |
| Pin 4 | CNTR-P (optional) | Repeater control signal positive |
| Pin 5 | DGND | Data ground (reference potential) |
| Pin 6 | +5 V | Regulated bus termination supply voltage |
| Pin 7 | +24 V (optional) | 24 V auxiliary voltage |
| Pin 8 | RxD/TxD-N (A-line) | Receive / transmit data negative (green core) |
| Pin 9 | CNTR-N (optional) | Repeater control signal negative |
Bus Termination
When Burkert 20136339 is placed at the physical start or end of a PROFIBUS segment, active bus termination must be provided via the +5 V (pin 6) and DGND (pin 5) connections using standard RS-485 termination resistor networks.

Burkert 20136339 incorporates 5 electronic modules equipped with digital inputs, providing 40 digital inputs (DI) in total. Each input module powers connected sensors with 24 V DC, limited to 30 mA per input channel. Sensors supported include 2-wire sensors (10–30 V), standard 3-wire PNP/NPN sensors, and volt-free mechanical limit switches.
| Input Parameter | Value |
|---|---|
| Switching Threshold Low ($V_{\text{OFF}}$) | 0 V to 5 V |
| Switching Threshold High ($V_{\text{ON}}$) | 10 V to 30 V |
| Input Current at $V_{\text{ON}}$ (typ. 24 V DC) | Max. 5.7 mA per channel |
| Input Impedance | > 4 kΩ |
| Diagnostic Functions | Open-circuit detection (2-wire), Short-circuit detection (3-wire) |
| Maximum Signal Cable Length | < 30 m |
| Permissible Wire Gauge | 0.14 mm² to 1.5 mm² (AWG 28 to AWG 16) |
| Galvanic Isolation | No (common reference potential for all channels) |
| Sensor Type Connected | Actuated State | Non-Actuated State | Short-Circuit State | Wire-Break State |
|---|---|---|---|---|
| 3-Wire Sensor | Reported | Reported | Detected / Reported | — |
| 2-Wire Sensor | Reported | Reported | — | Detected / Reported |
| Mechanical Limit Switch | Reported | Reported | — | — |

Burkert 20136339 features integrated check valves in exhaust ducts 3 (R) and 5 (S). These check valves prevent cross-pressurization and unexpected actuator movement caused by downstream backpressure peaks when several large cylinders exhaust simultaneously.
HotSwap Enclosure Clearance
To use the pneumatic HotSwap function and replace valves without interrupting main pressure supply 1 (P), maintain adequate clearance between the front of the valve island and the control cabinet door or front frame. Refer to the mounting diagram and ensure unhindered valve extraction during maintenance.
Commissioning with Bürkert Communicator
Parameter setting, diagnostic error readout, and mapping of cyclic PROFIBUS process values can be performed using the Bürkert Communicator software (Type 8920) in conjunction with the USB büS interface set (Article no. 772426).
| Description / Accessory | Article Number (Order Code) |
|---|---|
| Replacement Solenoid Valve Type 6534 CF-C (3/2-way NC, 24 V DC, screws included) | 20102334 (REF 20088974) |
| Electronic Display Module with Digital Inputs (8DI) | 384872 |
| Electronic Display Module without Digital Inputs | 384873 |
| ME43 Fieldbus Gateway Module — PROFIBUS DP | 301803 |
| 5-Pin Spring-Loaded Terminal Block (Logic & bus supply) | 920180 |
| 2-Pin Spring-Loaded Terminal Block (Valve AUX power) | 920442 |
| Fastening Screw Set M5 x 10 A2 DIN 6912 (Pack of 10) | 308661 |
| Height Adapter for 20-Fold Base without Intermediate Feed | 60041930 |
| Retaining Plate for 20-Fold Base without Intermediate Feed (Cabinet exterior) | 60005881 |
| Blind Plate for 20-Fold Base without Intermediate Feed | 60041931 |
| USB büS Interface Set 1 (for Bürkert Communicator Type 8920) | 772426 |