BURKERT 309093 (Type 8652) is a 12-slot AirLINE valve island featuring büS/CANopen communication, AirLINE Quick aluminium adapter plate, brass D10/D6 push-in ports, vacuum to 10 bar operation, and IP20/IP65 protection.

BURKERT 309093 (Type 8652) is a 12-slot AirLINE valve island configured with an AirLINE Quick anodised aluminium adapter plate and a 5-pin büS/CANopen communication interface. Developed for process automation, the assembly integrates twelve 11 mm solenoid valve positions consisting of six dual 3/2-way normally closed valves (Circuit Function C) and six 5/2-way monostable valves (Circuit Function H), delivering individual nominal flow rates up to 310 l/min.
The hardware design is optimized for direct installation onto the control cabinet floor or wall using the AirLINE Quick adapter, eliminating intermediate bulkhead fittings and significantly reducing cabinet volume requirements. Process safety features include external auxiliary pilot air supply operating between 3 and 10 bar, working pressure capabilities from vacuum down to -1.00 bar up to 10.00 bar, and integrated diagnostics reported on the local LC display as well as cyclically to the supervisory fieldbus controller.
| Technical Property | Specification Value |
|---|---|
| Product Type | Valve island Type 8652 AirLINE |
| Article Number | 309093 |
| Modular Platform Variant | Fieldbus module (Standard) |
| Number of Valve Slots | 12 PCE |
| Width per Station | 11 mm |
| Body Material | Polyamide (PA) |
| Seal Material | NBR and PUR |
| AirLINE Quick Adapter Material | Anodised aluminium |
| Supply Connection Port 1 | Push-in D10 mm, nickel-plated brass |
| Working Ports 2 and 4 | Push-in D6 mm, nickel-plated brass |
| Auxiliary Pilot Air Connection | External, 3...10 bar |
| Nominal Operating Pressure | -1.00 bar...10.00 bar (vacuum to 10 bar) |
| Nominal Flow Rate QNn (Air) | Up to 310 l/min (measured at +20 °C, 6 bar inlet, 1 bar pressure drop) |
| Operating Medium | Oil-free or lubricated compressed dry air, neutral gases (5 µm filtration recommended) |
| Compressed Air Quality | ISO 8573-1: 2010, Class 7.4.4 |
| Operating Voltage | 24 V DC (±10%), residual ripple 1 Vss |
| Nominal Power per Valve | 0.7 W (0.175 W after internal electronic power reduction) |
| Nominal Current per Valve | 29 mA (10 mA after power reduction) |
| Communication Protocol | büS / CANopen |
| Communication Hardware | 5-pin spring-loaded terminal strip |
| Valve Power Hardware | 2-pin spring-loaded terminal strip (AUX 24 V DC) |
| Protection Class | III according to DIN EN 61140, VDE 0140 |
| Degree of Protection | IP20 bare; IP65 mounted with AirLINE Quick in closed control cabinet |
| NEMA Enclosure Rating | Type 4X in closed enclosures (stainless steel variant) |
| Ambient & Medium Temperature | -10 °C...+55 °C |
| Storage Temperature | -20 °C...+60 °C |
| Digital Input Modules | 0 (without DI electronic module) |
| Intermediate Air Feed | 0 PCE (without intermediate supply module) |
Article 309093 is delivered fully assembled and factory tested with twelve Type 6534 pilot solenoid valves mapped across positions 1 through 12:
| Slot Position | Circuit Function | Valve Construction | Normal Position | Port Sizes | Operating Pressure |
|---|---|---|---|---|---|
| Slot 1 | CF-C | 2x 3/2-way solenoid valve | Normally closed | D6 push-in | Vac...10 bar (pilot 3...10 bar) |
| Slot 2 | CF-C | 2x 3/2-way solenoid valve | Normally closed | D6 push-in | Vac...10 bar (pilot 3...10 bar) |
| Slot 3 | CF-C | 2x 3/2-way solenoid valve | Normally closed | D6 push-in | Vac...10 bar (pilot 3...10 bar) |
| Slot 4 | CF-C | 2x 3/2-way solenoid valve | Normally closed | D6 push-in | Vac...10 bar (pilot 3...10 bar) |
| Slot 5 | CF-C | 2x 3/2-way solenoid valve | Normally closed | D6 push-in | Vac...10 bar (pilot 3...10 bar) |
| Slot 6 | CF-C | 2x 3/2-way solenoid valve | Normally closed | D6 push-in | Vac...10 bar (pilot 3...10 bar) |
| Slot 7 | CF-H | 5/2-way solenoid valve | Monostable | D6 push-in | Vac...10 bar (pilot 3...10 bar) |
| Slot 8 | CF-H | 5/2-way solenoid valve | Monostable | D6 push-in | Vac...10 bar (pilot 3...10 bar) |
| Slot 9 | CF-H | 5/2-way solenoid valve | Monostable | D6 push-in | Vac...10 bar (pilot 3...10 bar) |
| Slot 10 | CF-H | 5/2-way solenoid valve | Monostable | D6 push-in | Vac...10 bar (pilot 3...10 bar) |
| Slot 11 | CF-H | 5/2-way solenoid valve | Monostable | D6 push-in | Vac...10 bar (pilot 3...10 bar) |
| Slot 12 | CF-H | 5/2-way solenoid valve | Monostable | D6 push-in | Vac...10 bar (pilot 3...10 bar) |
The Type 8652 platform supports standardized pilot pneumatic circuit functions based on Type 6534 solenoid valves. Article 309093 implements Circuit Functions C and H as primary control elements:
All standard valves include manual overrides with latching and spring-return operation.
AirLINE Quick allows direct flush mounting of the valve terminal onto the control cabinet floor or wall, penetrating the enclosure boundary with sealed pneumatic connections.


Dimensions for 4-, 8-, and 12-slot configurations without intermediate supply:
| Variant | Dimension A (mm) | Dimension B (mm) | Mounting C | m (Stations) | n (Base Elements) |
|---|---|---|---|---|---|
| 4-fold | 66 | — | 4 x M5 | 3 | 1 |
| 8-fold | 35 | 111 | 8 x M5 | 7 | 2 |
| 12-fold (Article 309093) | 77 | 154 | 10 x M5 | 11 | 3 |
For 16-, 20-, and 24-slot platforms, the terminal expands modularly with optional intermediate supply blocks (dimension D = 114.3 mm or 158.3 mm) and up to 10 x M5 mounting points.

Mounting is supported either directly on a standard DIN rail conforming to EN 50022 (35 x 7.5 mm or 35 x 15 mm) or via the AirLINE Quick cutout on the control cabinet base.
Article 309093 operates with dedicated galvanic separation between fieldbus communication electronics and pneumatic solenoid power circuits.

The 5-pin spring terminal provides power to the internal communications processor, display unit, and CAN-based büS line:
| Pin Position | Terminal Marking | Core Colour | Signal Assignment |
|---|---|---|---|
| Pin 1 | +24 V DC | Red | Logic power supply (+24 V DC) |
| Pin 2 | CAN_H | White | büS / CAN_H signal line |
| Pin 3 | SHIELD | Green | Cable shield connection |
| Pin 4 | CAN_L | Blue | büS / CAN_L signal line |
| Pin 5 | GND | Black | Logic ground (0 V DC) |
Maximum supported conductor cross-section is ≤ 1.5 mm².
CANopen Bus Termination Requirement
CANopen and büS network segments require a 120 Ω terminating resistor at each end of the bus line. When the system is de-energised, the measured resistance between CAN_H and CAN_L across the network must be approximately 60 Ω.
The interface plate incorporates an independent 2-pin spring-loaded terminal strip to power the 24 V DC pneumatic coils:
| Terminal | Wire Colour | Assignment |
|---|---|---|
| Clip 1 | Red | AUX +24 V DC (valve coil supply) |
| Clip 2 | Black | GND (0 V DC valve return) |

When positioning the valve island inside the control cabinet, clearance dimensions must be preserved to permit replacement of individual valve slices and access to manual overrides without removing the island.
AirLINE Quick Control Cabinet Installation
Maintain the manufacturer minimum clearance distances between the valve terminal and the cabinet door/front edge. Adhering to these clearances ensures that pneumatic modules and electronic sub-assemblies can be serviced without unbolting the baseplate.

Article 309093 communicates over the CANopen-based büS platform within Bürkert's Efficient Device Integration Platform (EDIP). A Type 8652 equipped with Industrial Ethernet (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, or CC-Link IE Field Basic) can function as a fieldbus master, controlling downstream büS slave valve islands in a coordinated subsystem.

Commissioning, diagnostics, and firmware maintenance are carried out via the Bürkert Communicator software (Type 8920). Connecting a PC to the büS port requires the USB büS interface set (article no. 772426 or 772551). The software provides:
When ordered with applicable explosion protection configurations, Type 8652 valve islands comply with international standards for Zone 2/22 and Division 2 environments:
| Certification Agency | Marking Code | Standard / Certificate |
|---|---|---|
| ATEX | II 3G Ex ec IIC Gc II 3D Ex tc IIIC Dc | BVS 20 ATEX E 031 U |
| IECEx | Ex ec IIC Gc Ex tc IIIC Dc | IECEx BVS 20.0024 U |
| UL Listed (USA / Canada) | Industrial Control Equipment | UL 61010-1, CAN/CSA-C22.2 No. 61010-1 |
| cURus HazLoc (USA / Canada) | Class I, Zone 2, AEx ec IIC Gc / Ex ec IIC Gc U Class II, Zone 22, AEx tc IIIC Dc / Ex tc IIIC Dc U Class I, Div 2, Grp A, B, C, D Class II, III, Div 2, Grp F, G | ANSI/ISA 12.12.01, CSA C22.2 No. 213 |
| CCC (China) | Ex ec IIC Gc / Ex tc IIIC Dc | GB/T 3836.2021 series (SITIIAS) |
Hazardous Location Electrical and Hot Swap Restrictions
For Zone 2 / Zone 22 installations, the valve terminal must be installed inside an enclosure providing a minimum ingress protection of IP54 (for Category 3G gas atmospheres) or IP6X (for Category 3D dust atmospheres). Transient overvoltage protection must prevent voltage spikes exceeding 140% of the nominal peak supply. Terminals and push-in plugs must not be connected or disconnected while energised in the presence of an explosive atmosphere.
| Circuit Function | Width | Flow Rate QNn | Pressure Range | Opening Time | Closing Time | Voltage | Article No. (incl. screws) |
|---|---|---|---|---|---|---|---|
| CF-C (2x 3/2 NC) | 11 mm | 270 l/min | Vac...10 bar | 15 ms | 15 ms | 24 V DC | 301374 (REF 296031) |
| CF-H (5/2 monostable) | 11 mm | 290 l/min | Vac...10 bar | 20 ms | 25 ms | 24 V DC | 301376 (REF 296033) |
| CF-D (2x 3/2 NO) | 11 mm | 310 l/min | Vac...10 bar | 15 ms | 15 ms | 24 V DC | 301375 (REF 296032) |
| CF-Z (5/2 bistable) | 11 mm | 290 l/min | Vac...10 bar | 20 ms | 25 ms | 24 V DC | 301377 (REF 296034) |
| CF-L (5/3 closed) | 11 mm | 275 l/min | Vac...10 bar | 15 ms | 15 ms | 24 V DC | 301380 (REF 296036) |
| CF-M (5/3 ventilated) | 11 mm | 300 l/min | Vac...10 bar | 20 ms | 20 ms | 24 V DC | 301379 (REF 296035) |
| CF-N (5/3 exhausted) | 11 mm | 300 l/min | Vac...10 bar | 20 ms | 20 ms | 24 V DC | 301381 (REF 296039) |
| Dummy valve plate | 11 mm | — | — | — | — | — | 335779 (REF 327614) |
| Accessory Description | Quantity | Article No. |
|---|---|---|
| Retaining plate for control cabinet exterior (12-slot, without intermediate supply) | 1 | 60005567 |
| Height adapter plate (12-slot, without intermediate supply) | 1 | 754961 |
| Blind plate for cabinet floor cutout (12-slot) | 1 | 754966 |
| Screw set M5 x 10 A2 DIN 6912 (fastening island to cabinet base) | 10 | 308661 |
| 5-pin spring-loaded terminal strip (büS / communication power) | 1 | 920180 |
| 2-pin spring-loaded terminal strip (pneumatic valve power) | 1 | 920442 |
| USB büS interface set 1 (Type 8923) for Bürkert Communicator | 1 | 772426 |
| Terminating resistor büS / CANopen (direct plug-in) | 1 | 303833 |
Explore similar products in our catalog