Yoshitake HV-3 radiation and return valve for cold and hot water radiators. Features a completely closed fluororesin disc, small handle torque, and bronze body.

Yoshitake HV-3 is used as a radiation valve and return valve for cold and hot water heat radiators. It is commonly used in building and housing applications.


| Application | Cold and hot water |
|---|---|
| Maximum pressure | 0.6 MPa |
| Maximum temperature | 90℃ |
| Connection | Inlet: JIS Rc screwed Outlet: JIS R screwed (union joint) |
Materials
| Part | Material |
|---|---|
| Body | Bronze |
| Valve | Fluororesin |
| Brass | Brass |
TIP
When using the return valve, remove the handle after adjusting the flow rate as needed.
| Nominal size | d | L1 | L2 | L3 | H1 | H2 | H3 | D | Weight (Angle type) | Weight (Straight type) |
|---|---|---|---|---|---|---|---|---|---|---|
| 15A | 1/2 | 56 | 25 | 53 | 24 | 59-63 | 65-69 | 10 | 0.29 | 0.31 |
| 20A | 3/4 | 63 | 28.5 | 59.5 | 28 | 62-68 | 70-76 | 13 | 0.41 | 0.47 |



| No. | Part Name | Material |
|---|---|---|
| 14 | Gasket | EPDM |
| 13 | Union Nut | Brass (C3771) |
| 12 | Union Nipple | Brass (C3771) |
| 11 | Set Screw | Carbon Steel (SWRM) |
| 10 | Spring Washer | Carbon Steel (SWRH) |
| 9 | Handle | Nylon 66 (66NG) |
| 8 | Gland Nut | Brass (C3604) |
| 7 | Gland | Brass (C3604) |
| 6 | Packing | Non-Asbestos |
WARNING
Tightening pressure of the packing may decrease during transportation and storing. In this case, please additionally fasten the gland nut before using the valve. If external leakage has been neglected, leakage may not stop by additional tightening. Please check the valve daily and do the additional fastening earlier.