BURKERT 702523 Type 8640 modular valve island for pneumatics. Features 19mm width per station, G 1/4 pressure port, 3/2 valve function, and collective socket module for 2-8 bar operation.

The BURKERT 702523 Type 8640 valve unit system is designed to solve diverse and complex control problems due to its systematic modular construction and combination of pneumatic and electrical interfaces. This specific model features a 19 mm width per station, a 12-bank configuration, G 1/4 pressure ports, and a collective socket module. By putting together a row of pneumatic modules, multiple valve functionalities can be realized on one valve unit. The valves allow different applications to be covered, controlling neutral media and compressed air reliably.

The valves consist of a 3/2-way pilot valve (Type 6106) with different electrical connection variants, a valve body with diaphragm, seat seals, and A/B connection plates. The working ports 2 (B) / 4 (A) as well as the supply connection and exhaust port 1 (P) / 3 (R) are available with internal threads, plug-in couplings, or pointed hose nipples. A manual override is included for manual activation of the valve.

Components:
The valves can be mounted on the modular, pneumatic type MP05 base rails to form valve blocks. Any installation position is possible, preferably with the solenoid actuator on top.
To operate the valve manually, press the manual override and turn it 90° clockwise (until it stops). The manual override is locked and does not reset automatically.
WARNING
Only operate the manual override when the power is off.

To convert the 4/2-way valve to a 3/2-way valve, depending on the desired circuit function, close port 2 or port 4 with a stopper.

| Port 2 | Port 4 | Circuit function |
|---|---|---|
| closed | open | C |
| open | closed | D |
INFO
Pilot pressure for the pneumatic control unit depends on the pressure of the flow medium; it must be between 2 ... 10 bar (at least 70% of operating pressure).
INFO
Pressure difference between port 1 and 3 must be at least 2 bar. When temperatures are below 0 °C, operation is restricted to dried air.
| Parameter | Value |
|---|---|
| Ambient temperature | -10 ... +55 °C |
| Medium temperature | -10 ... +50 °C |
| Medium | Filtered compressed air (particle size max. 10 μm), preferably unlubricated; neutral gases (5 μm filtering) |
| Seal material | NBR |
| Operating pressure range | 2 ... 10 bar |
| Parameter | Value |
|---|---|
| Electrical connection | Cable plug Type 2516 on the plug contacts of the coil (torque for fastening: 1 Nm). |
| Voltage tolerance | ±10% |
| Degree of protection | IP65 (only in conjunction with cable plug Type 2516) |
| Cable plug | Can be mounted offset by 180° for the cable outlet selected. |
TIP
Important information to ensure functional reliability during continuous operation: If continuous operation is interrupted, a minimum activity of 1-2 switching operations per day is recommended for the duration of the downtime.

Standard rail installation:
Wall installation: Fasten the valve block directly to the wall with M4 screws.
Observe the following tightening torques when screwing into the port connections. The specified tightening torque may vary depending on the sealing system.
| Port size | Marking/function | Recommended tightening torque [Nm] | Maximum tightening torque [Nm] |
|---|---|---|---|
| G1/4, NPT1/4 | P, R/S connection | 4...7 | 20 |
| G1/8, NPT1/8 | P, R/S connection, A/B valve outlets | 3...6 | 7 |
DANGER
Risk of injury due to high pressure and escaping medium. Switch off the pressure before working on the device or system. Vent or drain the pipes.
Before connection:
Pneumatic connection: Push the hose lines into the push-in connections of the solenoid valves until they come to a stop. Use PTFE tape or elastomer seal for sealing the threaded connection. Align hose lines and connect the supply and working lines to the valve block.
DANGER
Risk of injury due to electric shock. Switch off voltage before working on the device or system. Secure against reactivation. When screwing in the solenoid with the cable plug, make sure that the seal is properly seated.

Screw on the cable plug observing the maximum tightening torque of 0.3 Nm. Check that the seal is correctly fitted. Connect the protective conductor and check electrical continuity between the coil and housing.
| Fault | Possible cause | Remedy |
|---|---|---|
| Valves do not switch | No operating voltage or operating voltage too low | Check electrical connection. Ensure operating voltage according to type label. |
| Manual override not in zero position | Bring manual override to zero position. | |
| Pressure supply insufficient or not available | Set up large-volume pressure supply. Minimum operating pressure ≥ 2 bar. | |
| Valves switch with a delay or blow off at the exhaust ports | Pressure supply insufficient or not available | Set up large-volume pressure supply. Minimum operating pressure ≥ 2 bar. |
| Valves are not in the home position (de-energised) during pressure build-up | Apply pressure to the valve block before the valves are switched. | |
| Insufficient ventilation of the exhaust air ducts due to too small or dirty silencers | Use suitably sized silencers or expansion vessels. Clean the dirty silencers. | |
| Impurities or foreign matter in the pilot or pneumatic valve | Apply pulsed pressure to the exhaust air ducts to blow out the impurities. Install a new pilot or pneumatic valve. | |
| Leaky valve blocks | Missing or crushed O-rings between the modules | Identify leak or missing seals. |
| Missing or incorrectly positioned flat seals between valve and base plate | Insert missing seals or replace damaged seals. |